13

Features

•  As pure sine wave inverter for all purposes
•  As PFC battery charger for typed battery
•  Automatic bypass function
•  Uninterrupted AC power (UPS function)
•  Continuous output power without derating « 70°C
•  Power Control – Dealing with limited generator, shore side or grid power to avoid sudden loads on generator causing voltage spikes
•  Power Support – Boosting the capacity of shore or generator power, an innovative feature of the Combi-3
•  Four stage adaptive charger and dual battery charging
•  LCD display for parameter setting and error messages
•  Programming auxiliary relay (x 3)
•  Programming input current limit for power share
•  User friendly parameters setting for power control and sharing
•  Wall Mount and Table Mount available for choices
•  Optional remote panel with LCD display for easy operation in distance

Generator-with-turbine

 

Specification

Explanation

Model C3-1500-12X
C3-1500-24X
C3-1500-48X
C3-3000-12X
C3-3000-24X
C3-3000-48X
Ventilation Forced cooling
Operation Tempreture -20   ~ +70
Humidity 0~95% (non condensing)
Cont. Power Output (W) 1500w (C3-1500)
3000w (C3-3000)
Input Voltage Range (VDC) 12V-(9.5 -16V) / 24V(19-32V) / 48V-(38-64V)
Output Voltage (VAC) 210~245 VAC / 94~128 VAC
Maximum Power (W) 3000w (C3-1500)
6000w (C3-3000)
Input Frequency 45-55Hz /55-65 Hz
Charge Characteristic 4-stage adaptive / Bulk-Absorption-Float-Equalize+Safe
Input Voltage Range (VAC) 180~265 VAC / 94~138 VAC
Output Charge Voltage (min ~ max) 8V~16V / 11V~32V / 22V~64V
AC IN Terminal Circuit Breaker 30A (110V) /15A (230V) (C3-1500)
30A (110V) /15A (230V) (C3-3000)
Detection Time AC Input Fault 4 ~10 milli-secs